Portable and Wheeled Fire Extinguisher Servicing
To ensure your fire extinguishers are in good condition and easily accessible, they should;
- Be hung on the wall between 1.0m and 1.2m and should be unobstructed.
- Be identified by a fire extinguisher sign written in English and Khmer.
- Be serviced every 6 months, with records kept.
- Have operating instruction on the front of the fire extinguisher.
- Be serviced, refilled, or possible replaced after use.
FIRESAFE has invested in a full range of professional testing and servicing equipment and can offers the following servicing package for fire extinguishers which is in accordance with AS 1851-2012 Section 10.
6 MONTHLY SERVICING
This must occur once per year, opposite to the Annual Servicing. (example 6 monthly servicing in January each year and annual servicing in July each year).
FIRESAFE conducts our fire extinguisher servicing in accordance with Australian Standards 1851:2005, Tables 15.4.1, 15.4.2, and 15.4.3.
As part of the 6 Monthly Service fire extinguishers will be;
- Inspected to ensure they are correctly hung.
- Inspected for visible damage or deterioration to ensure they are in good physical condition.
- Inspected to ensure instruction label is readable and clear.
- Inspected to ensure pressure gauge displays correct charge and is not damaged.
- Inspected to ensure anti tamper seal is in place.
- Inspection of safety pin.
- Inspection of signage.
- Check for free movement of Dry Powder.
- Cleaned to ensure longevity of fire blanket.
- Taged and stamped.
A comprehensive log of testing should be kept to ensure faults can be monitored and rectified.
ANNUAL SERVICING
This must occur once per year, opposite to the 6 Monthly Servicing. (example 6 monthly servicing in January each year and annual servicing in July each year).
As part of the 6 Monthly Service fire extinguishers will be;
- Inspected to ensure they are correctly hung.
- Inspected for visible damage or deterioration to ensure they are in good physical condition.
- Inspected to ensure instruction label is readable and clear.
- Inspected to ensure pressure gauge displays correct charge and is not damaged.
- Inspected to ensure anti tamper seal is in place.
- Inspection of safety pin.
- Inspection of signage.
- Check for free movement of Dry Powder.
- Cleaned to ensure longevity of fire blanket.
- Taged and stamped.
- Weighed for correct volume of extinguishing product.
A comprehensive log of testing should be kept to ensure faults can be monitored and rectified.
5 YEARLY OR AFTER USE SERVICING – HYDROSTATIC TEST
This must occur within 5 years of the date of manufacture or previous hydrostatic test. Fire Extinguisher will need to be removed and tested at FIRESAFEs Service Centre.
As part of the 5 Yearly Service fire extinguishers will be;
- Emptied and powder inspected.
- Internally and externally inspected for visible damage or deterioration to ensure they are in good physical condition.
- Inspected to ensure instruction label is readable and clear.
- Replace all O rings and perishable seals.
- Hydrostatically tested to ensure no pressure leaks.
- Clean and inspect all components of extinguisher.
- Refilled and reassembled.
- Repressurised with Nitrogen gas.
- Replace safety pin and anti tamper seal.
- Taged and stamped.
- Weighed for correct volume of extinguishing product.
- If extinguisher has been used or powder is not in good condition replacement of powder will be an additional cost to the client.
A comprehensive log of testing should be kept to ensure faults can be monitored and rectified.